Single Input/Output Module

The SIO800 Addressable Single Input/Output Module is an MX addressable module that provides one clean contact input and a voltage free changeover relay output. The input supports normally-open or normally-closed contacts and short/open circuit faults — depending on the input mode selected by the Control and Indicating Equipment (CIE). The relay is controlled by a command sent from the CIE via the MX addressable loop. The LED illuminates when the input goes into alarm, and can also be programmed to blink when polled by the CIE.

The MX1 CIE supports the following modes for the input circuit:

• Normally-open contact, closing for alarm, with open circuit fault.

• Normally-open contact, closing for alarm, with short and open circuit fault.

• Normally-closed contact, opening for alarm, with short circuit fault.

• Normally-closed contact, opening for alarm, with short and open circuit fault.

 

Use with MX1.

Details

Part No. 555.800.063

Specifications:

Operating Voltage1 20 to 40Vdc*
Quiescent Current 300µA (max.)
Alarm Current 3mA (max, LED on)
Circuit Resistance 50 Ohm
Relay Contact Rating 2A @ 24Vdc (max.)
EOL Resistor 3k3 Ohm
Alarm Resistor 680 Ohm
Ambient Temp -25 to +70°C
Relative Humidity 10% to 95% (n/cond)
Dimensions (HWD) 61 x 84 x 25mm
ActivFire Listed afp-3168
FPANZ Listed VF/671
CIE Compatibility MX1-Au, MX1-NZ

SIO800

Related Products

Smoke Detector Cages

The STI-8200-SS Series smoke detector cages are available in flush...

Wire Guard

W500 Series detector cages are available in a range of...

SR-90 – The Intelligent System for Physical Speed Reduction

SR-90 is a smart system for speed reduction of vehicles...

SR-BALI-BASE

SR-BALI-BASE is a cutting-edge product that allows the installation of...