Detector Input Module

The DIM800 Detector Input Module interfaces two collective detector circuits onto the MX addressable loop. Each circuit can support 3mA of detector quiescent current and requires a 4k7 Ohm End Of Line resistor.

The two circuits may be recognised as a single point (MX4428) or two separate points (MX1). Refer to the specific MX fire alarm panel specification. Unused circuits must be terminated with an ELD resistor.

The DIM800 requires a suitably rated and separately protected external 24V supply to power the detector circuits.

 

Use with MX1, MX4428, 4100ESi.

Details

DIM800

Specifications
Operating Voltage1 20 to 40Vdc
Quiescent Current 280µA (max.)
Loop Alarm Current 2.8mA (max.)
Ambient Temp -25°C to +70°C
Relative Humidity 10% to 95% (n/cond)
Detector Load 3mA (max per input)
Detector ELD 4k7 Ohm
External Supply2 20 to 28.7Vdc
Ext. Current/Circuit 7.5mA (normal)
Ext. Alarm Current3 30 to 50mA
Dimensions (HWD) 61 x 84 x 25mm
ActivFire Listed afp-3179
FPANZ Listed VF/643