The 4090-9101 Zone Adaptor Module Monitor ZAM allows a 2-wire circuit of conventional smoke or heat detectors to be interfaced on to the IDNet loop. Up to 20 conventional heat and smoke detectors can be monitored by a 4090-9101 Monitor ZAM. The address is set by DIP switch under the re sealable label. Note the 4090-9101 requires a separate 24Vdc power supply to power the conventional circuit.
Specifications
Comms Power1 24 to 40Vdc w/data
Operating Voltage 18.9 to 32Vdc
ZAM Current @ 24Vdc2
Quiescent 16mA max.
Alarm 72mA max.
Supervision Resistor 3k3 Ohm 1W
Dimensions (HWD) 105x105x35mm
Ambient Temperature 0 to +49°C
Relative Humidity 10% to 93% (n/c)