The 4090-9002 Relay IAM allows the CIE to control a remotely located Form “C” Relay contact using IDNet addressable communications for both data and module power. Typical applications are for switching local power for control functions such as magnetic door holders, or control of HVAC components, pressurisation fans, dampers, etc. Relay contact status is also communicated to the CIE. The address is set by DIP switch under the resealable label.
Specifications:
Comms Power1 24 to 40Vdc w/data
Relay Contact Ratings SPDT
0.5A @120VAC2
2A@24Vdc3
1A@24Vdc4
Current Limited Op 1k8/4k7 0.5W
Dimensions (HWD) 105x105x35mm
Ambient Temperature 0 to +49°C
Relative Humidity 10% to 93% (n/c)
1. IDNet communications with data
2. Transient suppressed load
3. Inductive load
Note: Loop powered 2 wire device
+612 9700 1050
sales@esdr.com.au
Unit 7 / 30 Perry Street, Matraville NSW 2036
Sign up to our newsletter