This IDNet addressable device provides a supervised, addressable interface to conventional warning devices such as sounders or strobes. The Signal IAM requires a supervised power supply or compatible signal input for powering the externally connected loads.
• Provides a single switched branch with supervision
• Contact is fused at 0.5A for 30V DC or 70V AC. Uses standard 20 x 5mm cartridge fuse
• EOLR is 10k.
• DC loads must be diode isolated
• Supervision cannot be disabled
• The supply side and the internal fuse are not supervised by the Signal IAM
• Signal IAM is not suitable for switching 100V audio signals